NE | The name of the NE, given in the NEM Configurator. |
Alarm Id | The format is “NE name:index”. The index is incremented for each new alarm in the NE, normally providing a unique identification. The index is reset to 1 if the NE is deleted and recreated. |
Alarm On Time | The date and time when FOXMAN‑UN received the alarm. This can be later than the actual occurrence in the NE. The occurrence time is also recorded and can be seen in the Alarm Properties. The default date and time format is yyyy/MM/dd - HH:mm:ss. The date and time format can be set in the “$NEM_HOME/etc/NMS.properties” file. |
Alarm Off Time | The date and time when FOXMAN‑UN received the alarm cleared message. Only applicable when calling the list for cleared and unacknowledged alarms from the Alarm Summary |
Localization | The unit, its card slot and the layer-subunit or port identification. An asterisk preceding the localization indicates the presence of a comment which can be viewed and modified in the Alarm Properties. |
Fault Cause | A text describing the type of alarm. The layer-subunit identification given in the localization columns also has to be considered. The fault cause text can be modified by the user via the Alarm Customisation |
Severity | The name of the alarm Severity. In addition the background of the text line for the alarm assumes the color assigned to its severity. |
Status | Shows “Outstanding” for a currently active alarm or “Cleared” for an inactive, but not yet acknowledged alarm. When a cleared alarm is acknowledged, it is moved to the Alarm List History. The history is accessible from the NEM Network Browser only. |
Ack Status | The Acknowledgment Status shows whether an alarm has been observed and dealt with by a FOXMAN‑UN user. It can have the values Not Ack'd (not acknowledged) or Ack'd (acknowledged). A status “Not Ack'd” causes the relevant symbol on a map and the relevant severity counter in the Alarm Summary to flash, advertising that there is a new alarm to be dealt with. |
NE Location | The location of the NE, as entered as part of the NE’s system configuration, where available. |
Type | The type of alarm. |
Work Instructions | When entered in the Alarm Customisation dialog work instructions are shown here. |
Ack’d By | For acknowledged alarms the user name that acknowledged the alarm is shown here. |